Comparing Techniques for Estimating Flame Temperature of Prescribed Fires

Abstract

A variety of techniques that estimate temperature and/or heat output during fires are available. We assessed the predictive ability of metal and tile pyrometers, calorimeters of different sizes, and fuel consumption to time-temperature metrics derived from thick and thin thermocouples at 140 points distributed over 9 management-scale burns in a longleaf pine forest in the southeastern US. While all of these devices underestimate maximum flame temperatures, we found several to be useful for characterizing other metrics of fire behavior. While the degree to which thermocouples underestimated maximum temperatures was based on thickness, metrics derived from thermocouple data that integrated time and temperature minimized this discrepancy between thin and thick thermocouples. Thermocouples also provided the most detailed spatial and temporal data of the devices tested. Pyrometers underestimated maximum temperatures relative to thermocouples, but due to their low cost, can be useful for examining spatial variation in temperature during fires. Use of calorimeters is disadvantageous given their lack of precision and high labor cost. Simple fire behavior observations taken during burns and indicators of fire severity observed post-burn were inexpensive to estimate and revealed useful differences among fires. Due to the wide variation among these techniques in cost, labor, accuracy, and level of detail of results, their suitability for a particular project will vary according to research objectives and available resources. Researchers should ensure that the fire behavior parameter measured has a logical relationship to the effect of interest, is measured at an appropriate level of detail, and is reported with attention to the limitations of the measuring devices used.

Introduction

Estimating flame temperature and duration has become increasingly common in studies of the ecological effects of fire. Researchers have found estimates of fire temperatures and their durations correlate well with fire effects on specific plant parts (seeds, roots, cambium) or soil components (e.g., Auld and O’Conner 1991, Dickinson and Johnson 2001). Time-temperature curves are most commonly measured using thermocouples deployed with data loggers. However due to the high cost of data loggers, researchers often rely on less expensive tools such as pyrometers or calorimeters to provide an index of flame temperature or heat release. Pyrometers, namely pellets, paints, or crayons manufactured to melt or change colors at specific temperatures, are commonly used to estimate fire temperatures in ecological studies (Fonteyn et al. 1984, Hobbs et al. 1984, Gibson et al. 1990, Cole et al. 1992, Franklin et al. 1997, Lippincott 2000, Menges and Deyrup 2001, Iverson et al. 2004). Calorimeters have been used to estimate heats of vaporization by measuring water mass lost from open containers exposed to fire (Beaufait 1966, Knight 1981, Moreno and Oechel 1989, Perez and Moreno 1998).

This suite of techniques commonly used by fire ecologists vary considerably in cost, level of detail of results, and most importantly accuracy. Notably, few of these instruments measure actual flame temperatures (or heat release in the case of calorimeters) as is sometimes erroneously reported in the ecological literature, but rather measure their own temperature during a fire (e.g. the device temperature), or their own heat gain in the case of calorimeters. While the device temperature is a function of the heat flux it receives from the fire and therefore highly correlated with physical aspects of fire, it is also a function of the device’s heat budget (heat gained — heat lost). The accuracy of different devices in measuring flame temperatures (or heat release) will therefore vary considerably due to their different heat budgets, which is influenced by their size, color, and material construction. In most cases, these devices are sensitive to heating duration and therefore underestimate true maximum flame temperature. The data they provide represents more accurately an integration of flame temperature and duration. Yet this fact does not necessarily diminish their utility for characterizing useful fire behavior parameters. In many cases, parameters that integrate time and temperature are more useful for predicting ecological effects than maximum temperatures, since instantaneous maximum temperatures in forest fire flames should all attain the same value (approximately 1100 C; Martin et al. 1969) regardless of rate of spread, flame length, flame width, etc… (Van Wagner and Methven 1978).

Due to the variation among these techniques in accuracy, cost, level of detail in results, and the amount of labor required for deployment, their suitability for a particular project will vary depending on research objectives and available resources. Where resources do not allow sophisticated measuring tools, and research or management objectives do not require them, rather simple measuring devices may be used as practical alternatives. In order for fire ecologists or fire managers to choose the best possible tool to meet their needs, they must be aware of the advantages and drawbacks of the suite of tools available.

Two recent studies compared values reported from pyrometers and calorimeters to a variety of metrics derived from time-temperature curves as measured by thermocouples (Perez and Moreno 1998, Wally et al., in press). Here, we extend these studies by comparing the predictive ability of two thicknesses of thermocouples, two types of pyrometers, and two sizes of calorimeters to the same time-temperature metrics as those used by Perez and Moreno (1998) and Wally et al. (in press). Because thermocouples, pyrometers, or calorimeters are either too expensive or too labor intensive to deploy in many management scenarios or landscape-level research projects, we also compare the time-temperature metrics to a simple field estimate of fuel consumption. Finally, we provide a cost and labor comparison of these techniques.

Methods

Site description

This study was conducted in naturally regenerated longleaf pine (Pinus palustris) stands at the Solon Dixon Forestry Education Center (SDFEC) in the lower coastal plain of Alabama, USA. The SDFEC is intensively managed for both wood production and research purposes. Of the Center’s 2,144 ha, approximately 23% are upland and bottomland hardwoods, 40% upland mixed pine-hardwoods, 33% even-aged pine plantations, and 4% regenerating cutover areas. In addition to longleaf pine, overstories of the stands used in this study contained loblolly pine (Pinus taeda), southern red oak (Quercus falcata), post oak (Quercus stellata), laurel oak (Quercus laurelfolia), and turkey oak (Quercus laevis). Understories are predominately shrubs (10–20% cover), with yaupon hollow (Ilex vomitoria), Vaccinium spp., and gallberry (Ilex glabra) comprising the dominant shrub species. Grasses (5–10% cover) include Andropogon spp., Panicum spp., Dicanthelium spp., among others. All of the stands used in this study were managed with early-growing season burns on a three-year rotation since the mid-1970s.

Average summer and winter temperatures at the SDFEC are 26° C and 9° C, respectively. Annual precipitation is 148 cm. Soils are deep and well-drained sandy loams that are strongly to very strongly acidic with low organic matter.

Sampling design

The data used in this study were collected during prescribed burns of 9 experimental plots (10–20 ha each) of the Fire Fire Surrogate (FFS) Study (http://www.fs.fed.us/ffs). The FFS Study uses a common experimental design at 13 sites across the United States to compare the ecological and economic consequences of fuel reduction treatments: an untreated control, mechanical treatments, prescribed burning, and a combination of mechanical treatments followed by prescribed burning. The Gulf Coastal Plain FFS at the SDFEC has an additional fifth treatment of an understory herbicide application followed by prescribed burning. For this study, we used 3 burn-only plots, 3 thin-and-burn plots, and 3 herbicide-and-burn plots. The burn-only treatment plots were burned in April and May of 2002. The thin-and-burn treatment plots were thinned during the fall of 2001 and burned in April and May of 2002. Understory fuels in the herbicide-and-burn treatment plots were treated with herbicide in the fall of 2002 and burned in April and May of 2003. Plots were burned with a combination of backing fires and spot fires, with distance between spots ranging from 20–50 m. In one of the burn-only plots the wind shifted and the fire developed into a flanking then heading fire. The broader implications of how the four fuel reduction treatments in the FFS study affect actual fuel loads and reduce the risk of catastrophic wildfire, the primary objective of the FFS study, will be the focus of a separate paper. Our focus of this paper is the comparison of different techniques for estimating flame temperature.

At systematically arranged sampling points in each of these 9 plots we installed thermocouples, metal and ceramic tile pyrometers, calorimeters, and visually estimated preburn fuel loads and fuel consumption postburn. Methods used for each of these techniques are described below. Sampling intensity varied among the 9 burns (Table 1); additional sampling points consisting of only calorimeters and pyrometers were used in the burn-only and herbicide-and-burn plots so that spatial patterns of fire temperature could be examined for a separate study. In this study, we only focus on sampling points where thermocouples were deployed with calorimeters and pyrometers (140 sampling points).

For reasons explained in the introduction, we refer to the measurements as TC temperature (thermocouple temperature), MP temperature (metal pyrometer temperature), TP temperature (tile pyrometer temperature), and C heat uptake (heat uptake by calorimeters).

Table 1 Number of thermocouple/datalogger pairs, pyrometers, and calorimeters used in each of 9 prescribed burns at a longleaf pine site in southern Alabama.

Thermocouples

We used HOBO® Type-K Thermocouple loggers equipped with high temperature stainless-steel Type-K Thermocouple probes (Onset Computer Corporation, Cape Cod, MA, USA). The data loggers are easily buried due to their small dimensions (6 × 8 × 1.5 cm). They are battery powered and store data on a microchip. Only thick thermocouple probes (4.8 mm diameter) were used for the 6 burns conducted in 2002. These probes consisted of a 304 stainless steel jacket packed with MgO, with an isolated Type K thermocouple junction at the tip. For 2 herbicide-and-burn plots burned in 2003, both thin (1 mm diameter) and thick diameter thermocouple probes were compared at a subset of points. At these points, the tips of the thin and thick probe thermocouples were positioned within 2 cm apart. At all points, loggers were placed in PVC tubes (8.8 cm wide, 13.2 cm long) with plastic caps on each end and buried below the soil surface. To prevent damage to loggers, litter and other available fuels were removed within 50 cm of the point of burial. Thermocouple cables were buried in soil 5–10 cm deep between probes and loggers. Fuels within 1 m of the thermocouple probes were left in their natural state as far as was possible. Data loggers were programmed to record temperature every 2 seconds (4 plots) or 3 seconds (5 plots).

Tile Pyrometers

We painted 4” ceramic tiles with Tempilaq® heat indicating lacquers designed to melt at specific temperatures (Tempil Division, Big Three Industires, Inc., South Plainsfield, NJ, USA). Based on previous burns, we selected 14 lacquers that melted over a range of temperatures from 79 −427° C at increments of 28° C. Several days before each burn, tile pyrometers were installed at sampling points by securing them with wire to a metal conduit stake at 30 cm height. This height was selected because previous trials measuring temperatures at 0, 30, and 100 cm height indicated average fire temperatures were highest at 30 cm (Kennard, unpublished). Tiles were protected from rain with plastic bags; bags were removed the morning of burns.

Calorimeters and Metal Pyrometers

We used pint-sized (2002 burns) or half-pint sized (2003 burns) rectangular tin cans with screw caps (Yankee Containers, North Haven, CT, USA) for calorimeters. These particular cans were chosen because they were inexpensive (65–86 cents/ea.), had screw caps useful for transporting water, and would not melt at high temperatures unlike aluminum cans. We applied the same 14 different lacquers used for tile pyrometers around the top of each can (metal pyrometer). Calorimeters were wired to metal stakes at 30 cm height (opposite tile pyrometers) several days before burns and protected with plastic bags. On the day of burns, we removed plastic bags and put 50 ml of water in each can. After prescribed burns were completed, cans were capped, collected, and transported to the lab where remaining water was measured with a graduated cylinder or weighed. For each burn, 2–3 control calorimeters were placed in unburned areas to account for ambient evaporation. The amount of water vaporized from caloriometers during burns (accounting for ambient evaporation) was used to estimate heat uptake by cans as: heat uptake = [(80 cal/g water) × (g water)] +[(540 cal/g water) × (g water)], where 80 cal are needed to raise each gram of water from 20° C to boiling point and 540 cal are need to vaporize each gram of water (Beaufait 1966).

Fuel consumption estimates

Fuel loads were estimated within 3 weeks before burns in 1 m2 subplots centered on the sampling points. In each subplot, the percent cover and average height of live trees/shrubs, dead trees/shrubs, vines, grasses, and forbs were estimated and used to calculate volumes. Biomass for these various fractions was then estimated using regression models derived from 150 1-m2 plots (located in the same treatment units) where the same method was used to estimate fuel volumes before fuels were destructively sampled and the dry masses determined: live tree/shrub (biomass g [ln+1] = 0.552 volume (cm3) + 0.104, r2 = 0.63), dead tree/shrub (biomass g [ln+1] = 0.462 volume (cm3) + 0.295, r2 = 0.52), vines (biomass g [ln+1] = 0.423 volume (cm3) + 0.515, r2 = 0.53), grasses (biomass g [ln+1] = 0.475 volume (cm3) + 0.360, r2 = 0.53), and forbs (biomass g [ln+1] = 0.420 volume (cm3) + 0.100, r2 = 0.54). Litter depth was measured in the center of the subplot. Litter mass was calculated from depth using a litter density of 0.039 g/cm3 derived from 900 1ft2 plots that were destructively sampled in the same treatment units. In a 1 m transect bisecting the subplot, the number of intercepts of fuels in four size classes (0–.6 cm, .6–2.5 cm, 2.5–7.6 cm, > 7.6 cm) were counted. Number of intercepts were used to calculate volumes and masses (assuming an overall density of 0.01 g/cm3) of these down woody fuels using Brown’s equations (Brown 1974). Immediately following fires, the percent burn of each subplot was visually estimated.

Statistical analysis

Following Perez and Moreno (1998) and Wally et al. (in press) we calculated six metrics of TC temperatures:

  1. 1.

    One-minute mean about the maximum (MEAN);

  2. 2.

    Instantaneous maximum (MAX);

  3. 3.

    Time elapsed where instantaneous maximum > 60° C (TIME60);

  4. 4.

    Time elapsed where instantaneous maximum > 150° C (TIME150);

  5. 5.

    Integrated area under the instantaneous maximum curve over a threshold of 60° C (AREA60); and

  6. 6.

    Integrated area under the instantaneous maximum curve over a threshold of 150° C (AREA150).

As reported in Wally et al. (in press), the time elapsed during which the maximum temperature exceeds 150° C has been associated with calorimeter data (Perez and Moreno 1998), and the 60° C threshold corresponds to lethal temperature for plant cells (Alexandrov 1964).

We evaluated how closely pyrometers and calorimeters estimated the various metrics of TC temperatures by running linear regressions using each of the six metrics as response variables in separate analyses. We also evaluated which combinations of fuel components (standing fuel mass, down woody debris mass, litter mass), with or without pyrometer and calorimeter data, could predict TC temperatures by running forward multiple regressions in separate analyses using each of the thermocouple metrics. For each of these analyses, we use metrics derived from the thick thermocouples as the independent variable. Statistical analyses were performed using SPSS v. 9.0 (SPSS, Inc. 1998).

Results

Summary statistics of weather conditions and standard descriptions of fire behavior are presented for each burn in Table 2. These simple observations show some variation among burns. For example, the burns in Plots 2 and 10 were slower moving fires with higher residence times and shorter flames than the other 4 plots. The burns in plots 6 and 12, in contrast, were relatively faster moving fires, with higher flame lengths and wider flaming zones.

Table 2 Weather conditions and standard fire behavior parameters observed during the 9 prescribed burns conducted in spring of 2002 and 2003 in southern Alabama.

Thermocouples

Table 3 shows summary statistics of metrics calculated from thin and thick thermocouples. As shown in Figure 1, the increase in TC temperature to the maximum peak is slower in thick than in thin thermocouples due to the higher heat capacity of thick probes. Due to this slow response time, the maximum TC temperature is underestimated by thick thermocouples relative to the thinner thermocouples, particularly at high temperatures (Figure 2). These delayed responses are also reflected in the differences in TIME60 and TIME150 between the thick and thin thermocouples. Metrics that integrate time and temperature (MEAN, AREA60, and AREA150) were not as sensitive to delayed response times and therefore were very similar when measured by thick or thin thermocouples.

Figure 1
figure 1

Time x temperature curves for thin (0.1 cm diameter) and thick (0.48 cm diameter) thermocouples installed at a single point 30 cm above ground during a prescribed burn in longleaf pine in southern Alabama.

Figure 2
figure 2

Scatterplots and R2 values from regression analyses of six metrics derived from thin (0.1 cm) and thick (0.48 cm) thermocouples installed 30 cm above ground during two prescribed burns in a longleaf pine forest in southern Alabama (N = 21).

Table 3 Summary statistics of metrics derived from thermocouples, pyrometers, caloriometers, and fuel assessments. Only burned points, defined as more than half of the 1 m2 plot burned, are included in these statistics.

Pyrometers

Pyrometers were best at predicting MEAN and MAX TC temperature, explaining 61 to 68% of the variation in these metrics (Table 4, Figure 3). Pyrometers explained approximately 43 to 52% of the variation in TIME150, AREA60, and AREA150 TC temperature, and were worst at predicting TIME60 TC temperature (Table 4). Observer bias in how pyrometers were tallied was evident when comparing burns from 2002 and 2003. In 2002, tile and metal pyrometers underestimated MAX TC temperature by an average of 45° C and 14° C, respectively. In 2003, tile pyrometers underestimated MAX TC temperature by an average of 9° C, but metal pyrometers overestimated MAX TC temperature by an average of 51° C. If 2002 and 2003 burns are analyzed separately for metal pyrometers, adjusted R2 improve 3 to 18% (Table 4).

Figure 3
figure 3

Scatterplots of metal and tile pyrometer temperatures and: A. one-minute mean about the maximum thermocouple temperature (MEAN) as measured by thick thermocouples, or B. instantaneous maximum temperature (MAX) as measured by thick thermocouples.

Table 4 Adjusted R2 values from linear regression analyses of metal pyrometer temperature, tile pyrometer temperature, and caloriometer heat uptake on six metrices calculated from thick thermocouple data. For metal pyrometers, results are also analyzed separately for 2002 and 2003.

Calorimeters

Calorimeters were generally poor predictors of the thermocouple metrics, explaining only 12 to 36% of the variation in MEAN, MAX, TIME60, TIME150, AREA60, and AREA150 TC temperatures (Table 4, Figure 4). However, calorimeters did provide some information that pyrometers did not— the addition of calorimeter data to multiple regression models improved predictions of both MEAN and AREA60 TC temperatures. The size of cans used for calorimeters affected the amount of water vaporized-large cans tended to lose more water than small cans at points with similar thermocouple metrics. Information derived from control cans set out during each burn was not useful for accounting for ambient evaporation on a per sample basis. Approximately 25% of calorimeters showed no water loss or a water gain with the correction for ambient evaporation. This suggests small-scale variation in ambient evaporation complicates applying a single correction factor to many samples over a large area. As an example of this variation, the amount of water evaporated from control cans and cans retrieved from unburned points ranged from 6 to 22% (n = 23) of initial water content.

Figure 4
figure 4

Scatterplots of net heat uptake of caloriometers and A. one-minute mean about the maximum thermocouple temperature (MEAN) as measured by thick thermocouples, or B. instantaneous maximum temperature (MAX) as measured by thick thermocouples.

Fuel consumption indices

Pre-burn fuel load estimates were generally poor predictors of thermocouple metrics; only three (litter depth, intercepts of fuel > 7.6 cm diameter, calculated mass of down woody debris) were significant in multiple regression models (Table 5). Percent burn was more important in models predicting MEAN TC temperature than any of the fuel load estimates. The addition of metal pyrometers and calorimeters improved models, explaining 81% and 66% of the variation in MEAN and AREA60 TC temperatures, respectively.

Table 5 Multiple regression results of fuel load estimates and percent burn on two thermocouple metrics (MEAN and AREA60) derived from thick thermocouples. Regressions were run both with and without pyrometer and caloriometer data in models.

In Table 6, we summarize the estimated costs, times for deployment, levels of detail in data output, and appropriate uses of these different techniques. We also include, where applicable, a ranking of how closely these devices estimate instantaneous maximum temperatures.

Table 6 Estimated cost, time for deployment, detail, precision, and accuracy of data, and typical uses of 7 techniques for estimating fire temperature, heat output, or fire severity. Infrared cameras, while not included in this study, are included here for comparison purposes.

Discussion

The variety of techniques commonly used to estimate temperature or heat output of fires (thermocouples, pyrometers, calorimeters, and estimates of fuel consumption) vary considerably in cost, required labor, accuracy, and level of detail of results (Table 6). The thin and thick thermocouples used in our study both underestimated maximum temperatures, but to varying degrees. Neither size of thermocouple consistently approached degrees of 1100° C, the accepted instantaneous maximum temperature of flames in forest fires (Martin et al. 1969). It is well known that the thickness and other physical attributes of thermocouples influence their heat budgets, and therefore their ability to accurately measure flame temperatures and residence times (Stocks and Walker 1968, Gill and Knight 1991, Dickinson and Johnson 2001, Iverson et al. 2004). Considerably thinner thermocouples than those used in this study would be required to detect maximum temperatures and residence times more accurately. However, this necessarily creates a compromise between thermocouple wires that are sturdy enough to withstand field use but thin enough to register quick temperature changes. We found that using certain metrics that integrate time and temperature (e.g., MEAN, AREA60, AREA150) minimized these differences caused by thermocouple thickness. These metrics may prove more useful for predicting fire effects than instantaneous maximum temperature, since the duration of heat exposure is a significant variable determining cell death in plants and microbes, and the consumption of soil organic matter. The particular thick probes used in our study have also proved useful in estimating fireline intensity (Bova and Dickinson 2003). One noted advantage of using HOBO dataloggers is that their small size and relatively lower cost allowed us to sample extensively over the burn area, overcoming a common disadvantage of other datalogger types that restrict sampling to small areas (Wally et al. in press). Iverson et al. (2004) also noted this advantage of this particular datalogger type in their landscape-scale study of prescribed fires in oak-hickory forest.

Given their lower cost as compared to thermocouples, pyrometers predicted MEAN and MAX (as measured by the thick thermocouples) relatively well, explaining 60 to 82% of the variation of these metrics. The fact we used the thicker thermocouples as the reference for comparison in this study underestimates the degree of inaccuracy of pyrometers in detecting maximum temperatures. We found tile pyrometers to be less accurate than metal pyrometers due to the insulating affect of the ceramic tiles. This insulating affect is particularly noticeable if the flame front approaches the tile pyrometer on the face opposite the painted surface. The water in our metal pyrometer/calorimeters absorbed heat creating an insulating affect as well, although this effect was less than that caused by the ceramic tiles. A significant drawback to the use of pyrometers is the inconsistent behavior of paints and the subjective interpretation of melted paints. Some paints melted poorly, even at temperatures above their designed melting point. Charring of the pyrometer surface made paints difficult to read. And, paints behaved differently on different material (e.g., soaked into porous ceramic, dripped on metal). These limitations, and the influence of pyrometer construction material, make comparison of pyrometer results across studies questionable.

We found calorimeters were generally poor predictors of thermocouple metrics. While these results are similar to those found by Wally et al. (in press), they contrast with those of Perez and Moreno (1998) who found calorimeters more accurate than pyrometers. In our study, calorimeters were not useful for comparing small differences in fire intensity, partly due to the confounding effects of small-scale variation in ambient evaporation. Water condensation from smoke may have been another source of error. Another disadvantage is that calorimeters cannot distinguish low fire intensities, making them useful only for coarse scale differences in fires of higher intensity than our study. Because the size and shape of cans and the amount of water used will affect the heat budget of calorimeters, comparing values from different calorimeters across studies is also unreliable.

Pre-burn fuel load estimates were not useful for predicting thermocouple metrics. This was surprising considering the patchiness of fuels, particularly in the 3 plots that were thinned before burning. In contrast, a simple post-burn assessment of percent burn explained up to 36% of variation in thermocouple metrics. The predictive ability of this simple post-burn assessment of fuel consumption would likely be improved by including completeness of burn for different fuel components (litter/duff layer, woody debris, standing fuels), similar to commonly used post-burn severity classifications (Hungerford 1996). While not reliable for determining fire temperature, post-burn assessments may be suitable for assessing coarse-scale burn characteristics particularly over large areas and under limited budgets.

Due to the wide variation among these techniques in cost, labor, accuracy, and level of detail of results, their suitability for a particular project should depend on research objectives and available resources. Fire researchers and/or fire managers may rarely have the funds, labor, and time to choose the most accurate tool possible, but their objectives may not always require such accuracy. For example, physiological studies of fire damage to tree cambial tissue requires a different set of techniques than a study of the impact of fuel management on fire behavior over entire stands. Notably, the simple fire behavior observations taken during the burns (flame height, rate of spread, residence time, etc…) revealed useful differences among the nine fires. While these techniques are easy, inexpensive to estimate, and can give adequate descriptions of management-scale burn impacts, we have noted that many fire research publications do not report these parameters. Minimally, studies should report these fire behavior parameters so that managers can replicate burns and their desired effects more easily or alter burn prescriptions to avoid undesirable outcomes. Where thermocouples, pyrometers, or calorimeters are used in fire research, authors should be careful to note the limitations of these devices when reporting results.

References

  • Alexandrov, V.Y. 1964. Cytophysical and cytological investigations of heat resistance of plant cells toward the action of high and low temperature. Quarterly Review of Biology 39:35–77.

    Article  Google Scholar 

  • Auld, T.D., and M.A. O’Conner. 1991. Predicting patterns of post-fire germination in 35 eastern Australian Fabaceae. Australian Journal of Ecology. 16:53–70.

    Article  Google Scholar 

  • Beaufait, W.M. 1966. An integrating device for evaluating prescribed fires. Forest Science. 12:27–29.

    Google Scholar 

  • Bova, A.S. and M.B. Dickinson. 2003. Making sense of fire temperatures: a thermocouple heat budget correlates temperatures and flame heat flux. In Abstracts 88th Annual Meetings. The Ecological Society of America: Savanna GA. 40–41.

    Google Scholar 

  • Brown, J.K. 1974. Handbook for inventorying downed woody material. USDA Forest Service Intermountain Forest and Range Experiment Station GTR INT-16. Ogden UT 24 pp.

  • Cole, K.L., K.F. Klick, and N.B. Pavlovic. 1992. Fire monitoring during experimental burns at Indiana Dunes National Lakeshore. Natural Areas Journal. 12:177–183.

    Google Scholar 

  • Dickinson, M.B., and E.A. Johnson. 2001. Fire Effects on Trees. In ‘Forest Fires: Behavior and Ecological Effects.’ (Eds EA Johnson, K Miyanishi). Academic Press: San Diego. 477–526.

    Chapter  Google Scholar 

  • Fonteyn, P.J., M.W. Stone, M.A. Yancy, and J.T.G. Baccus. 1984. Interspecific and intraspecific microhabitat temperature variations during a fire. American Midland Naturalist 112:246–250.

    Article  Google Scholar 

  • Franklin, S.B., P.A. Robertson, and J.S. Fralish. 1997. Small-scale fire temperature patterns in upland Quercus communities. Journal of Applied Ecology 34:613–630.

    Article  Google Scholar 

  • Gibson, D.J., D.C. Hartnett, and G.L.S. Merrill. 1990. Fire temperature heterogeneity in contrasting fire prone habitats: Kansas tallgrass prairie and Florida sandhill. Bulletin of the Torrey Botanical Club, 117:349–356.

    Article  Google Scholar 

  • Gill, A.M., and I. Knight. 1991. Fire Measurement. In ‘Conference on Bushfire Modeling and Fire Danger Rating systems.’ (Eds NP Cheney, AM Gill) (CSIRO Division of Forestry, Yarralumla, ACT) 137–146.

    Google Scholar 

  • Hobbs, R.J., J.E..P Currall, and C.H. Gimingham 1984. The use of ‘thermocolor’ pyrometers in the study of heath fire behavior. Journal of Ecology 72:241–250.

    Article  Google Scholar 

  • Hungerford, R.D. 1996. Soils. Fire in Ecosystem Management Notes: Unit II-I. USDA Forest Service, National Advanced Resource Technology Center, Marana, Arizona.

    Google Scholar 

  • Iverson, L.R., D.A Yaussy, J. Rebbeck, T.F. Hutchinson, R.P., Long, and A.M. Prasad. 2004. A comparison of thermocouples and temperature paints to monitor spatial and temporal characteristics of landscape-scale prescribed fires. International Journal of Wildland Fire. 13:1–12.

    Article  Google Scholar 

  • Knight, I.K. 1981. A simple calorimeter for measuring the intensity of rural fires. Australian Forestry Research. 11:173–177.

    Google Scholar 

  • Lippincott, C.L. 2000. Effects of Imperata cylindrica (L.) Beauv. (Cogongrass) invasion on fire regime in Florida sandhill. Natural Areas Journal. 20:140–149.

    Google Scholar 

  • Martin, R.E., C.T. Cushwa, and R.L. Miller. 1969. Fire as a physical factor in wildland management. In ‘Proceedings of the Ninth Annual Tall Timbers Fire Ecology Conference.’ Tall Timbers Research Station, Tallahassee, FL. 271–288.

    Google Scholar 

  • Menges, E.S., and M.A. Deyrup. 2001. Postfire survival in south Florida slash pine: interacting effects of fire intensity, fire season, vegetation, burn size, and bark beetles. International Journal of Wildland Fire. 10:53–63.

    Article  Google Scholar 

  • Moreno, J.M., and W.C. Oechel. 1989. A simple method for estimating fire intensity after a burn in California chaparral. Acta Oecologia Planta. 10:57–68.

    Google Scholar 

  • Perez, B., and J.M. Moreno. 1998. Methods for quantifying fire severity in shrubland-fires. Plant Ecology. 139:91–101.

    Article  Google Scholar 

  • SPSS, Inc., 1998. SPSS for Windows 9.0.0. SPSS Inc. Chicago, Illinois.

    Google Scholar 

  • Stocks, B., and J. Walker. 1968. Thermocouple errors in forest fire research. Fire Technology 4:59–62.

    Article  Google Scholar 

  • Van Wagner, C.E., and I.R. Methven. 1978. Prescribed fire for site preparation in white and red pine. In ‘White and red pine symposium: Chalk River, ON, September 20–22, 1977.’ (Compiler DA Cameron) Symposium Proceedings O-P-6. Sault Ste. Marie, ON: Department of the Environment, Canadian Forestry Service, Great Lakes Forest Research Centre. 95–101.

    Google Scholar 

  • Wally, A., E.S. Menges, and C.W. Weekley, (In press) Evaluating methods for measuring fire intensity at multiple scales in heterogeneous vegetation. Submitted to. Journal of Applied Ecology.

Download references

Acknowledgements

This research was funded by the USDA Forest Service through the National Fire Plan. Although the authors received no direct funding for this research from the U.S. Joint Fire Science Program (JFSP), it was greatly facilitated by the JFSP support of existing Fire Fire Surrogate project sites. The Solon Dixon Forestry Education Center conducted the burns. David Jones, Julie Arnold, Joe McConnell, Becky Estes, Lindsay Carnes, Cynthia Fowler, and Josh McDaniel assisted with fieldwork. We thank Louis Iverson and Tom Waldrop for the use of thermocouples.

Author information

Authors and Affiliations

Authors

Rights and permissions

Open Access  This article is licensed under a Creative Commons Attribution 4.0 International License, which permits use, sharing, adaptation, distribution and reproduction in any medium or format, as long as you give appropriate credit to the original author(s) and the source, provide a link to the Creative Commons licence, and indicate if changes were made.

The images or other third party material in this article are included in the article’s Creative Commons licence, unless indicated otherwise in a credit line to the material. If material is not included in the article’s Creative Commons licence and your intended use is not permitted by statutory regulation or exceeds the permitted use, you will need to obtain permission directly from the copyright holder.

To view a copy of this licence, visit https://creativecommons.org/licenses/by/4.0/.

Reprints and permissions

About this article

Cite this article

Kennard, D.K., Outcalt, K.W., Jones, D. et al. Comparing Techniques for Estimating Flame Temperature of Prescribed Fires. fire ecol 1, 75–84 (2005). https://doi.org/10.4996/fireecology.0101075

Download citation

  • Published:

  • Issue Date:

  • DOI: https://doi.org/10.4996/fireecology.0101075

Keywords